Circuit integrity test at 750 degrees for a minimum

period of 90 minutes. The pass criteria involve

maintaining circuit integrity, with no occurrence of

short circuits or breakages.

EN 50200

A circuit integrity test is conducted at 830 degrees with

mechanical shock every 5 minutes.

PH30: 30-minute test

PH60: 60-minute test

PH90: 90-minute test

PH120: 120-minute test

EN 50200 Annex E: This test is carried out, followed by

an 850-degree flame for 15 minutes with fire and

mechanical impact, followed by another 15 minutes with

mechanical impact and water spray.

BS 6387 CWZ

Tests are conducted under different scenarios to

evaluate the cable's performance.

Category C Test: The cable is exposed to fire for 3

hours at a flame temperature of 950 degrees.

Category W Test: The cable is exposed to fire with

water spray, involving 15 minutes of fire at 650

degrees followed by 15 minutes of both fire and

water spray.

Category Z Test: The cable is exposed to fire and

mechanical shock, with a flame temperature of 950

degrees and mechanical shock for 15 minutes.